Capacity: 3000 VA / 2700 W
Efficiency
Double coversion mode: 0.91
Eco Mode: Up to 98%
Input
Voltage range: 176-300V 100% load, 100-176V derating to 40% load linearly
Rated Frequency range: 50Hz-60Hz
Frequency range: 40Hz-70Hz(45Hz-55Hz 54Hz-66Hz @ load>60%)
Power factor: >0.99
THDI: <5%
Input connection: Wiring/socket IEC C19
Output
Rating Voltage: 220/230/240V
Rating Current: 45A
Frequency range Rated: 50Hz/60Hz
Frequency range: 40Hz-70Hz(45Hz-55Hz 54Hz-66Hz @ load>60%)
Maximum Power factor: 0.9
Voltage accuracy: ±1%
THDv: <2% linear load, <6% non-linear load
Transfer time: 0ms(4ms @ line , bypass;10ms @ ECO In- verter)
Crest Ratio: max 3:1
Overload (line mode): 100%
≤ 150% for 10 seconds. >150% for 0.3s.
Output connection Wiring/socket: 4 x IEC C13 + 1 x SA
Battery Voltage: 75VDC
Battery Capacity (AH): 6 x 12V/9Ah
Charger: Maximum charging current 1.5A
Other working mode: CVCF Yes (derating to 60% load)
HMI (human-machine interface)
Display: Segment LCD
USB: USB20.0
RS232: Yes
EPO: Yes
Intelligent slot: Yes
Network card: Yes, NMC mini card
Modbus card: Optional, CMC/Modbus Long Card
Dry contactor card: Optional, AS400 Long Card
Monitor software: Winpower
Dimension, D x W x H: 190mm x 393mm x 327mm
Net Weight: 22.7kg
IP protection level: IP20
Environmental and safety
EMC Standard: IEC/ EN 62040-2
Safety Standard: IEC/ EN 62040-1
Operation temperature: 0-40℃